A power-storage plant does not need a lithium-ion battery to store electricity. It can use ordinary air, compress it, cool it until it becomes a liquid, and later turn that liquid back into a gas to drive turbines.
This is the basic idea behind liquid air energy storage (LAES), a technology that reached an important engineering milestone in China on October 30, 2026. A 60 MW, 600 MWh demonstration facility in Golmud, Qinghai Province, was connected to the electricity grid and began generating power.
The project's reported power rating and energy capacity imply a nominal discharge duration of ten hours at full rated output. That makes it relevant to the wider search for long-duration energy storage, particularly in electricity systems that rely increasingly on variable solar and wind generation.
However, a grid connection is not the same as proof of commercial profitability, long-term reliability, or a particular round-trip efficiency. Understanding what the project demonstrates requires looking at the physics, engineering, and economics of storing energy as cryogenic air.
1. What Is Liquid Air Energy Storage?
Liquid air energy storage is a mechanical and thermal energy-storage technology. It uses electricity to compress and cool atmospheric air until a portion of it becomes liquid. The liquid is stored in insulated tanks and later expanded to produce electricity.
Unlike a conventional electrochemical battery, the system does not rely on a chemical reaction inside a battery cell to store energy. It relies on pressure, temperature, phase changes, heat transfer, and rotating machinery.
Air is a mixture of gases, mainly nitrogen and oxygen, with smaller amounts of other components. It can be purified, compressed, cooled, and liquefied using industrial cryogenic processes.
The technology is sometimes described as cryogenic energy storage because it stores air at extremely low temperatures.
2. What Happened in China in October 2026?
The Golmud demonstration project in Qinghai was connected to the grid and began generating electricity on October 30, 2026, according to the project commissioning contractor. The installation is rated at 60 MW of power and 600 MWh of energy capacity.
The China Energy Storage Alliance and industry reporting have described it as the largest grid-connected liquid-air energy storage project of its kind by rated power and energy capacity. That description refers specifically to liquid-air storage installations, not to all energy-storage technologies.
The project was developed by China Green Development Investment Group in cooperation with research organizations including the Technical Institute of Physics and Chemistry at the Chinese Academy of Sciences. Construction began in 2023, and the project was included in China's national new-type energy-storage demonstration program.
Understanding the two headline numbers
Power and energy capacity describe different things:
- 60 MW: The rated power output. It describes how quickly the facility can deliver electricity under the specified operating conditions.
- 600 MWh: The stated energy-storage capacity. It describes the amount of energy associated with the storage system.
Dividing 600 MWh by 60 MW gives ten hours. This is the nominal duration implied by the two ratings. It does not prove that the plant has already completed ten-hour discharge cycles continuously or that it can deliver the same output under every grid condition.
This distinction matters because energy-storage headlines often combine a power rating and an energy rating without explaining what each one measures.
3. How Liquid Air Energy Storage Works
A typical LAES installation operates through three broad stages: charging, storage, and discharge. Actual plant designs differ, but the basic thermodynamic process follows the same principles.
Stage 1: Charging — using electricity to liquefy air
When electricity is available at a time when demand or market prices are relatively low, the plant can use it to operate compressors.
Air is drawn into the system and purified to remove moisture, carbon dioxide, and other contaminants that could freeze or cause operational problems during cryogenic processing.
The compressors raise the air pressure. Compression generates heat, and an efficient design attempts to capture or manage that heat rather than simply discarding it.
The compressed air is then cooled through heat exchangers and a refrigeration or liquefaction process. At sufficiently low temperatures, part of the air becomes liquid and can be transferred into insulated storage tanks.
Liquid air is stored at very low temperature, close to atmospheric pressure in the storage vessels described for this type of system. The storage tanks are designed to limit heat entering the liquid from the surrounding environment.
Stage 2: Storage — keeping the air cold
The liquid air is held in insulated tanks until electricity is needed. The storage system must control heat transfer, pressure, boil-off, and operational safety.
Thermal management is not a secondary detail. The cold energy associated with liquefaction is one of the important resources that can improve the efficiency of the full process.
Some LAES designs use a separate cold-storage system to capture and reuse refrigeration energy during later operation. The objective is to avoid repeating as much of the cooling work every time the system is charged.
Stage 3: Discharging — turning liquid air into electricity
When the grid needs electricity, the liquid air is pumped to a higher pressure. It is then heated and vaporized through heat exchangers.
As the liquid becomes a gas, its volume increases substantially. The expanding gas can drive turbines connected to electrical generators.
The system may also recover cold energy released during vaporization and retain useful heat from the charging process. These thermal stores can be integrated into later cycles to improve performance.
The result is electricity generated through an industrial expansion process rather than through an electrochemical reaction.
4. Why Store Electricity as Liquid Air?
Long-duration storage
One of the strongest arguments for LAES is its potential to store energy over longer periods than many short-duration battery applications are designed to provide.
A system with a nominal ten-hour duration can shift electricity from one part of the day to another. This can be useful when solar generation is abundant during daylight hours but demand remains high after sunset.
It can also help manage periods when renewable generation and electricity demand do not occur at the same time.
Flexible siting compared with underground compressed-air storage
Some compressed-air energy-storage systems depend on suitable underground geological formations, such as salt caverns or other appropriate reservoirs.
Liquid-air storage uses insulated tanks above ground. This can offer greater flexibility in choosing a site, although the location still needs suitable land, industrial infrastructure, electricity connections, safety systems, and access to relevant services.
It would be inaccurate to say that LAES can be installed anywhere. It removes one important geological constraint, not every siting constraint.
Potential for industrial supply-chain development
LAES uses equipment that is related to established industrial fields, including compressors, expanders, heat exchangers, cryogenic systems, tanks, pumps, and control equipment.
Manufacturers and engineering companies may be able to apply existing expertise to the technology, although large-scale integration and long-term operating experience remain important challenges.
Use with renewable electricity
Wind and solar plants can produce electricity when generation exceeds immediate demand or when grid constraints limit how much power can be delivered.
Energy storage can absorb some of that surplus and return electricity later. This does not eliminate the need for transmission upgrades, demand response, flexible generation, or better grid planning, but it can become one part of a broader flexibility strategy.
5. The Efficiency Challenge
One of the most important questions for LAES is how much electricity can be returned compared with the electricity used to charge the system.
This is called round-trip efficiency. If a storage plant consumes 100 units of electricity during charging and later returns 55 units, its round-trip efficiency is 55 percent.
The remaining energy is lost through compression, heat transfer, refrigeration, pumps, turbines, generators, and other parts of the process.
Research published in the Journal of Energy Storage in 2025 examined different cold-storage configurations for LAES and reported modeled round-trip efficiencies that varied by system design. One analyzed configuration reached 60.7 percent, while a cascaded packed-bed configuration reached 53.4 percent under the study's modeled assumptions.
A separate 2026 analysis of liquefaction and expansion processes reported a modeled maximum round-trip efficiency of 54 percent for a particular optimized configuration.
These figures are research results for specific designs. They are not independently measured operating results for the Golmud facility.
Why cold storage matters
When liquid air is vaporized, it absorbs heat. If the system fails to recover and reuse useful cold energy, the next charging cycle may need to consume more electricity to reach the required temperature.
Thermal storage can therefore have a substantial effect on total performance. Researchers examine packed beds, phase-change materials, and other configurations to improve the way heat and cold are stored and transferred.
Better heat exchangers, compressors, expanders, and operating controls may also improve performance.
6. How LAES Compares With Other Energy-Storage Technologies
| Technology | Main storage mechanism | Potential strength | Main limitation |
|---|---|---|---|
| Lithium-ion batteries | Electrochemical reactions | Fast response and established supply chains | Degradation, material sourcing, and project economics over long durations |
| Pumped hydro | Water moved between elevations | Large-scale storage and long operating experience | Geography, permitting, construction time, and environmental impacts |
| Compressed-air storage | Pressurized air | Potential for large-scale storage | Some configurations depend on suitable geological formations |
| Liquid-air storage | Cryogenic liquid air | Potential for long-duration storage with flexible tank-based siting | Thermal-management complexity and conversion losses |
| Flow batteries | Electrolyte stored in tanks | Power and energy capacity can be scaled separately | System complexity, electrolyte cost, and efficiency differences by design |
No single technology is automatically the best option for every grid. A short-duration frequency-response application has different requirements from a ten-hour renewable-energy shifting project.
Utilities should compare storage systems using the complete cost of ownership, including construction, financing, charging electricity, operating expenses, maintenance, replacement, performance degradation, and end-of-life requirements.
7. What Could Prevent LAES From Becoming Widely Commercial?
Capital cost
Large compressors, cryogenic equipment, insulated tanks, turbines, and heat exchangers require substantial investment. The economic case depends on how often the system operates, how much electricity it can buy and sell, and whether it receives payments for grid services.
A demonstration project can establish that an engineering system can be built and connected. It does not automatically prove that the same design will earn an acceptable return in every electricity market.
Thermal complexity
LAES depends on managing heat and cold through multiple operating stages. Small losses in thermal integration can affect overall performance.
The plant must operate safely across different loads and environmental conditions, while its control systems coordinate compressors, expanders, heat exchangers, storage vessels, and grid connections.
Operational experience
Long-term reliability matters. Operators need evidence about maintenance intervals, equipment life, availability, startup behavior, performance under changing loads, and the cost of replacing major components.
These questions cannot be answered by a single grid-connection announcement.
Competition from other storage systems
Lithium-ion battery prices and manufacturing capacity continue to influence the economics of storage. Other technologies, including pumped hydro, flow batteries, thermal storage, and compressed-air systems, also compete for projects.
LAES must demonstrate a specific advantage in the duration, location, cost, or operating requirements of a project.
8. What the Golmud Project Should Be Watched For Next
The next important evidence will come from operating data rather than headline capacity figures.
Observers should look for independently reported information on:
- Actual charging and discharging schedules.
- Measured round-trip efficiency under defined conditions.
- Availability and maintenance requirements.
- Performance during partial-load operation.
- Thermal-storage effectiveness over repeated cycles.
- Operating costs and the value of electricity delivered.
- How the project supports local renewable generation and grid flexibility.
It is also useful to distinguish project design expectations from measured results. A developer may estimate annual electricity delivery or renewable-energy absorption, but these estimates should not be presented as independently verified annual performance before operating data are available.
Frequently Asked Questions
What is liquid air energy storage?
Liquid air energy storage uses electricity to compress and cool air until it becomes liquid. The liquid is stored in insulated tanks and later pressurized, heated, and expanded through turbines to generate electricity.
How long can the Golmud facility supply electricity?
Its stated ratings are 60 MW and 600 MWh, which imply a nominal ten-hour duration at full rated output. Actual operating duration depends on operating conditions and usable energy.
Is liquid air energy storage more efficient than lithium-ion batteries?
Not generally. Lithium-ion batteries often achieve higher round-trip efficiency. LAES may offer advantages in some long-duration or site-constrained applications, but the economic comparison depends on project conditions.
Does liquid air storage require underground caverns?
No. The technology stores liquid air in insulated tanks, which can provide greater siting flexibility than compressed-air designs that rely on specific underground formations.
Does the Golmud project prove that LAES is commercially mature?
No. It is a major grid-connected demonstration milestone. Commercial maturity requires additional evidence on reliability, efficiency, operating costs, and long-term performance.
Conclusion
Liquid air energy storage offers a different way to address one of the electricity system's central challenges: storing large amounts of energy and returning it when generation and demand do not align.
China's 60 MW, 600 MWh Golmud project is an important engineering milestone because it brings a large liquid-air system into grid-connected operation. Its tank-based storage approach could make long-duration storage possible in locations that are not suitable for some underground storage technologies.
But the next stage is more important than the headline. Operators must demonstrate reliable cycles, competitive costs, effective thermal management, and useful grid performance. Until those results are available, LAES should be viewed as a promising storage option under commercial evaluation—not a universal replacement for batteries or pumped hydro.
Sources
- China Energy Storage Alliance — World's Largest Liquid Air Energy Storage Project Connects to Grid in China
- pv magazine — World's Largest Liquid-Air Storage Facility Comes Online in China
- Huafeng Weiye — Commissioning of the Golmud 60 MW / 600 MWh Project
- International Energy Agency — Electricity 2026: Flexibility
- U.S. Department of Energy — Storage Innovations 2030
- Journal of Energy Storage — Comparative Analysis of Liquid and Solid-Based Cold Energy Storage Configurations
- Technical University of Denmark — Analysis of Liquefaction Processes for Liquid Air Energy Storage Systems